VAT 612 Series Installation, Operating, & Maintenance Instructions page 61

Butterfly pressure control valve with cc-link interface, dn 63-250 (i.d. 2.5" - 10")
Table of Contents

Advertisement

Signal
Name
Type
Signal
FATAL ERROR
Bitmap
GENERAL STATUS
Bitmap
GENERAL WARNING
Bitmap
EXTENDED WARNING
NOT USED (reserved)
Signal
NOT USED (reserved)
Bitmap
1) To adjust range refer to chapter: «Range of pressure and position values»
GENERAL STATUS bitmap table:
Bit
0
FIELDBUS DATA VALID
1
ZERO EXECUTED
2
PING PONG RX-BIT
3
PRESSURE SIMULATION
PRESSURE SETPOINT
4
REACHED
5-6
NOT USED (reserved)
7-8
ACCESS MODE
9
WARNINGS ACTIVE
10-15
NOT USED (reserved)
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 612 DN 63-250 (I.D. 2.5" - 10"), CC-Link
Start
Byte
Data
Word
Length
Type
unsigned
11
1
integer
boolean
16
2
array
boolean
17
2
array
boolean
18
2
array
19-22
1
23-24
1
0 = Output buffer data not valid
1 = Output buffer data valid
ZERO successful executed, active for 2 seconds
PING PONG RX BIT, is inverted and transmitted back to the fieldbus master (PLC), See chapter:
Communication and timing control between Master (PLC) and Station (Valve)
3.10.8
0 = off
1 = on
0 = The actual pressure is not within 2% of the pressure setpoint
1 = The actual pressure is within 2% of the pressure setpoint
-
bit 8
bit 7
0
0
= LOCAL
= REMOTE
0
1
= LOCKED
1
0
0 = No WARNINGS
1 = At least one WARNING of the warning bitmaps is active (GENERAL WARNING bitmap and
EXTENDED WARNING bitmap)
-
Valid
Range
20,21,22,25,40
-
-
-
-
Description
Description
20 = no stop detected during synch
mode
21 = valve blocked during synch mode
22 = valve blocked
25 = step loss during synch mode
40 = motor driver fault
See bitmap table below
See bitmap table below
See bitmap table below
-
-
289856EA
61/85
2011-07-06