VAT 612 Series Installation, Operating, & Maintenance Instructions page 51

Butterfly pressure control valve with cc-link interface, dn 63-250 (i.d. 2.5" - 10")
Table of Contents

Advertisement

3.10.2.3
Setpoint ramp adjustment
Setpoint ramp effects:
Undershoot of pressure
Response time
Default value for Setpoint Ramp is 0. Adjustment range for Setpoint Ramp is from 0 to 10 s.
This parameter defines the time that is used to decrease / raise pressure between 2 setpoints. Especially in pressure
decrease situations at low flows pressure response can be improved much by adapting setpoint ramp time.
Pressure chart
Without setpoint ramp optimizing
P
SF
S
P
START
P
EN
D
Choose the applicable formula depending on units you are familiar with.
t = Setpoint Ramp
Adjustment procedure:
1.
Start with optimal gain factor and sensor delay time according to preceding tuning steps.
2.
Control a typical pressure / flow situation.
3.
Control a lower pressure.
4.
Repeat from step 2 with longer setpoint ramps until best response is achieved.
5.
Verify pressure control response for a setpoint raise situation.
Note: In case a long ramp time is required to get optimal performance for pressure decrease situations it may be of
advantage to apply different settings for decrease / raise control situations.
Local operation:
('Control View', 'Control Performance Analyzer' or
Go to 'Setup / Control Parameter' menu.
Select setpoint ramp.
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 612 DN 63-250 (I.D. 2.5" - 10"), CC-Link
'Service Box 2')
With setpoint ramp optimizing
t
Remote
operation:
Note: It's not possible to do 'Setpoint ramp
adjustment' via CC-Link.