2.
Range of pressure and position values (optional)
The «range of pressure and position values» can be adjusted. That means:
For position values, the value for valve position "CLOSE" and the valve position "OPEN" can be set to a other
ones then the default 0...100'000 is.
For pressure values, the value for physical 0 Volt and 10 Volt of the sensor output can be set to other values
then the default 0...1'000'000 is.
The range of pressure and position values can be configured by 'Control View', 'Control Performance Analyzer' or
'Universal Hyper Terminal'.
The «set-command» is: «s:24xxytoz».
y: lower scale value, floating point, entry with a point '.' and '-' for negative values possible
z: upper scale value, floating point, entry with a point '.' and '-' for negative values possible
xx: signal number in the buffer
xx
Value
00
Pressure
01
Pressure sensor 1
Pressure sensor 2 (optional, only in
02
case of 2 sensor version)
03
Position
Not used – reserved
04
Not used – reserved
05
06
Pressure setpoint
07
Position setpoint
Not used – reserved
08
Not used – reserved
09
Not used – reserved
10
Not used – reserved
11
The «get-command» is: «i:24xx». The answer returns the range  «i:24xxytoz». The xx is the value number, y value is
the current lower scale value of buffer and value z the upper scale value.
The format of y and z has following syntax: _ _ _ _ _ _ _ _._ _ _ _ _
Examples:
i:2400-0012345.12345to00123456.12345
i:2401-0001000.00000to00001000.00000
i:240200001000.00000to00001500.00000
Example «get-command» with Terminal: Get the range of Pressure Sensor 1:
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 612 DN 63-250 (I.D. 2.5" - 10"), CC-Link
Default lower
scale value
0
0
0
0
-
-
0
0
-
-
-
-
Default range
Default
upper scale
value
1'000'000
1'000'000
1'000'000
100'000
-
-
1'000'000
100'000
-
-
-
-
Min/Max range
Min lower
Max upper
scale value
scale value
1'000'000
-1'000'000
1'000'000
-1'000'000
1'000'000
-1'000'000
1'000'000
-1'000'000
-
-
-
-
1'000'000
-1'000'000
1'000'000
-1'000'000
-
-
-
-
-
-
-
-
289856EA
2011-07-06
41/85