Assembly; Assembly Sequence - WAGO -I/O-SYSTEM 750 Manual

2-channel digital output module dc 24 v, shortcircuit protected, high-side switching. 2do 24v dc 2.0a
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-502 2DO 24V DC 2.0A
Po
s: 64 /Alle Serien (Allgemeine Module)/Überschriften für alle Serien/Montieren - Überschrift 1 @ 3\mod_1225446744750_21.doc @ 24900 @ 1 @ 1
4

Assembly

Po s: 65.1 /Serie 750 (WAGO-I/O-SYSTEM)/Montieren/Montagereihenfolge @ 3\mod_1231770210031_21.doc @ 25992 @ 2 @ 1
4.1

Assembly Sequence

All system components can be snapped directly on a carrier rail in accordance
with the European standard EN 50022 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual components are securely
seated on the rail after installation.
Starting with the coupler/controller, the bus modules are assembled adjacent to
each other according to the project design. Errors in the design of the node in
terms of the potential groups (connection via the power contacts) are recognized,
as the bus modules with power contacts (male contacts) cannot be linked to bus
modules with fewer power contacts.
Po s: 65.2 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Vorsicht/Vorsicht: Verletzungsgefahr durch scharfkantige Messerkontakte! @ 6\mod_1256193279401_21.doc @ 43414 @ @ 1
Risk of injury due to sharp-edged male contacts!
The male contacts are sharp-edged. Handle the module carefully to prevent injury.
Po
s: 65.3 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: Busklemmen in vorgegebener Reihenfolge stecken! @ 6\mod_1256194177073_21.doc @ 43429 @ @ 1
Connect the I/O modules in the required order!
Never plug bus modules from the direction of the end terminal. A ground wire
power contact, which is inserted into a terminal without contacts, e.g. a 4-channel
digital input module, has a decreased air and creepage distance to the neighboring
contact in the example DI4.
Po
s: 65.4 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: Aneinanderreihen von Busklemmen nur bei offener Nut! @ 6\mod_1256193351448_21.doc @ 43417 @ @ 1
Assemble the I/O modules in rows only if the grooves are open!
Please take into consideration that some bus modules have no or only a few power
jumper contacts. The design of some modules does not allow them to be
physically assembled in rows, as the grooves for the male contacts are closed at
the top.
Po
s: 65.5 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Hinweis/Hinweis: Busabschluss nicht vergessen! @ 6\mod_1256194225557_21.doc @ 43432 @ @ 1
Don't forget the bus end module!
Always plug a bus end module 750-600 onto the end of the fieldbus node! You
must always use a bus end module at all fieldbus nodes with the WAGO I/O
System 750 fieldbus couplers/controllers to guarantee proper data transfer.
Pos: 65.
6 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Manual
Version 1.2.0
Assembly
25

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-502

Table of Contents