WAGO -I/O-SYSTEM 750 Manual page 15

2-channel digital output module dc 24 v, shortcircuit protected, high-side switching. 2do 24v dc 2.0a
Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-502 2DO 24V DC 2.0A
contacts used as blade contacts. It then provides this potential to subsequent I/O
modules via the power contacts used as spring contacts.
Pos: 19.14 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheitshinweise/Achtung/Achtung: Maximaler Strom Leistungskontakte 10 A @ 3\mod_1226499143500_21.doc @ 25029 @ @ 1
Do not exceed maximum current via power contacts!
The maximum current to flow through the power contacts is 10 A.
Greater currents can damage the power contacts.
When configuring the system, ensure that this current is not exceeded. If
exceeded, an additional potential feed module must be used.
Po
s: 19.15 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Versorgung/Galvanische Trennung Feld/Syste
m @ 3\mod_1233756478750_21.doc @ 27102 @ @ 1
The field level and the system level are electrically isolated from one another.
Po s: 19.16 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Einsatzbereich/Hinweise/Warnung: Einsatz Variante /xxx-8xx in sicherheitsgerichteten Anwendungen @ 5\mod_1246882860453_21.doc @ 36680 @ @ 1
Using in safety related applications!
When using the I/O module ( 750-502 ) in safety-related applications, the
instructions and connection examples in Section "Use in safety-related
applications" are to be observed!
Po s: 19.17 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Versorgung/Anordnung bei Einsatz in sicherheitsgerichteten Anwendungen blockweise @ 5\mod_1246876694406_21.doc @ 36674 @ @ 1
Any configuration of the output modules is possible when designing the fieldbus
node. Grouping of module types is not necessary.
Po s: 19.18 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Einsatzbereich/Einsatzbereich 750-xxxx alle Koppler/Controller ohne Einschränkung @ 3\mod_1232541691906_21.doc @ 26522 @ @ 1
The I/O module 750-502 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.
Po s: 20 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Manual
Version 1.2.0
Device Description
15

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-502

Table of Contents