Protective Functions; Protective Function Table - Sanyo Denki SANUPS E11A Series Instruction Manual

Hybrid, 1kva, 1.5kva, 2kva, 3kva, 100v
Hide thumbs Also See for SANUPS E11A Series:
Table of Contents

Advertisement

Characteristics
§
1
7
.
2
P
§
1
7
.
2
P
(1) Overload protection
If the UPS output is overloaded by exceeding the current
capacity of the inverter, such as when a computer system
boots up, the output selector automatically switches the
source of AC power from the inverter to the bypass circuit,
without interruption.
After a certain period of time has elapsed, the source of power to the load is switched back to the inverter without
interruption (auto-return), as shown in §17.1(1).
* When "Overload Recovery Operation" in the user setting menu is set to "Bypass", the UPS switches to inverter
power supply without interruption when the overload is resolved.
(2) UPS fault protection
If a fault occurs in the UPS, the output selector activates automatically and switches to bypass power without
interruption. The "Red ALARM" indicator lights, and the alarm buzzer sounds. The power supply route is the same as
for an overload.
Output from the UPS will stop if a power outage occurs during bypass operation due to the UPS fault. Contact your
supplier or SANYO DENKI as soon as possible.
§
1
7
.
3
P
§
1
7
.
3
P
The following table shows functions and operations which activate to protect the UPS.
Item
Preparation
Normal
Serious failure
Overload
(effective value)
Forced bypass
Input over
voltage
Input over
voltage
(prolonged)
Power outage
Power outage
(prolonged)
Input error
(frequency)
Input error
(prolonged)
Battery failure
(*1): Buzzer sound patterns:
① *
② **......**......
③ **********......
④ ****......****...
(*2): In this state, the LED blinks or is off, depending on the setting of "UPS Operation at
setting menu.
When this setting is set to "Bypass"
When this setting is set to "OFF"
(*3): Battery operation. Stops inverter operation when final battery discharge is reached.
45
r
o
t
e
c
t
i
v
e
F
u
n
c
t
r
o
t
e
c
t
i
v
e
F
u
n
c
t
r
o
t
e
c
t
i
v
e
F
u
n
c
t
r
o
t
e
c
t
i
v
e
F
u
n
c
t
Operation panel (front panel) indicators
Green
Green
Green
INV.ON
INPUT
OUTPUT
STAND BY
(*2)
(*2)
Continuous tone
Continuous beeps
i
o
n
s
i
o
n
s
Utility
power
i
o
n
T
a
b
l
e
i
o
n
T
a
b
l
e
Alarms
Red
Buzzer
Red
Red
BATT.
ALARM
O.L
LOW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
:
: -
Inverter
Rectifier
Converter
Charger
Batteries
Indication of the marks in the table
are as follows.
Lit LED :
Blinking LED :
Buzzer Alarm : ① - ④
Protective
functions
(*1)
(UPS operations)
Rectifier, charger,
Power up
-
operation
Power up,
Inverter operation
-
operation
Stop inverter
Bypass supply
Auto return
Bypass supply
Manual switch
-
to bypass supply
Battery operation
Battery operation
(*3)
Stop rectifier and
Battery operation
charger
Inverter operation
Battery operation
(*3)
Battery operation
Battery operation
(*3)
Stop inverter
Bypass supply
Press
to stop the buzzer.
OFF" in the user
Output
Notes