Troubleshooting Modbus Communication - Carrier RTU Open v5 Integration Manual

Hide thumbs Also See for RTU Open v5:
Table of Contents

Advertisement

Communications wiring
Set the remaining DIP switches as follows:
4
Modbus DIP switch settings
8
Off
The following example shows the DIP switches set for 9600 baud and Modbus.
Connect the Modbus EIA-485 network to the RTU Open's J19 Network Comm port. Connect to Net+, Net-,
5
and SHLD.
Wire specifications
A dedicated 22 AWG shielded twisted pair wire (EIA 485)
Maximum wire length 2000 feet (610 meters) or 32 nodes
Devices should be daisy-chained and not star-wired
Attach the drain/shield wire to both ends of the network segment and through every controller
NOTE Use the same polarity throughout the network segment.
Turn on the RTU Open's power.
6

Troubleshooting Modbus communication

The most common communication problems result from not properly following the configuration steps outlined
above in this manual. Review all of the steps and use the following list to check your settings.
Verify accuracy of the following:
Hardware settings for speaking Modbus (8 Data bits, No Parity, and 1 Stop bit):
Baud rate DIP switches DS2 and DS1
Protocol DIP switches DS3 - DS6
RTU Open v5
Integration Guide
7
6
5
Off
Off
On
12
4
3
On
Off