Carrier RTU Open v5 Integration Manual page 46

Hide thumbs Also See for RTU Open v5:
Table of Contents

Advertisement

Appendix A: Network Points List for RTU Open
BACnet System
Points Display
Name
System Space
Temperature
System Space RH
System Space AQ
System OA
Temperature
[OA] Enthalpy
(BACnet)
System Outdoor AQ
System Water
Temperature
†System
Fire/Smoke
†System
Pressurization
Occupancy control
configuration
BAS On/Off*
(Occupancy)
Occupancy control
configuration ust be
set for 3 = BAS
On/Off
In the i-Vu® interface, select the controller in the navigation tree and go to Properties > BACnet Objects tab. When
an i-Vu® Open controller or a third party system writes to any of the system points, you must use BACnet Priority
Level 16 and the value must not be written to or refreshed more than once per minute (60 seconds).
CAUTION If any other Priority Level is used, the value will not be recognized by the controller.
* Modbus, N2, and LonWorks default values only apply to multi-protocol controllers.
† Points do not apply to multi-protocol controllers.
RTU Open v5
Integration Guide
Valid Range
BACnet/
Modbus
/N2 Default Value*
-50 – 150°F
1 – 100%
200 – 9999 ppm
-50 – 150°F
High (0) / Low (1)
200 – 9999 ppm
-50 – 150°F
Inactive (0) / Active (1)
Inactive (0) / Active (1)
1 = Always Occupied
2 = BACnet Schedule
(WebCTRL® only)
3 = BAS On/Off (third
party control)*
4 = Remote Occ Input
1=Inactive
2=Occupied
3=Unoccupied
LonWorks
Default Value*
-999
~180°F
-999
-15.96
-999
64537
-999
~180°F
Low (1)
Low (1)
-999
-999
-999
~180°F
Inactive (0)
N/A
Inactive (0)
N/A
1 = Always
N/A
Occupied
(Only available
through BACnet)
Inactive (1)
Inactive (1)
42
Recommended Write
Rrefresh
Time
(min/max)
1 min/5 min
5 min / 10 min
5 min / 10 min
5 min / 60 min
On change of state
5 min / 60 min
5 min / 60 min
On change of state
On change of state
N/A
On change of state
CARRIER CORPORATION ©2019
All rights reserved