Appendix A: Network Points List for RTU Open
Point Name
Point
Access
Input 8 Switch
R/W
Configuration
Input 9 Function
R/W
Input 9 Switch
R/W
Configuration
Number Of Heat Stages
R/W
Occupancy Source
R/W
Space sensor type
R/W
Space Temp Source
R
Unit Type
R/W
ZS Temp Sensor
R
Economizer Operation
R
Space Temperature
R
Alarm Status
SPT Sensor
R
SPT Sensor
R
input_10
R
Factory Test Analog 1
R/W
Control
Economizer High OAT
R/W
Lockout Temp
Maximum Heating SAT
R/W
RTU Open v5
Integration Guide
Units
Default
Value
2=Enthalpy
Switch
3=Fan Status
4=Filter Status
5=Remote
Occupancy
6=Door Contact
1=NO
1
2=NC
1=No Function
2
2=HumidiStat
3=Fan Status
4=Filter Status
5=Remote
Occupancy
6=Door Contact
1=NO
1
2=NC
1=1
2
2=2
3=0
1=Always
1
Occupied
2=BACnet
Schedule
3=BAS On/Off
4=Remote Occ
Input
1=T55
1
2=T56
3=SPT Sensor
4=None
1=Sensor Failure
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
1=Heat / Cool
2
2=LC
WeatherExpert
3=HP O/B Ctrl
4=HP Y1/W1 Ctrl
0=Normal
1=Alarm
0=Normal
1=Fault Detected
0=Normal
1=Alarm
°F
min
°F
%
0
°F
75
°F
120
50
BACnet
BACnet Point Name
BACnet
Object ID
di8_type
MSV:81018
di9_function
MSV:81009
di9_type
MSV:81019
heat_stages
MSV:91004
occ_source
MSV:1002
spt_type
MSV:9001
spt_status
MSV:2003
unit_type
MSV:9018
zst_sensor_fail
BV:7051
econ_opr
BV:7054
spt_alrm_status
BV:7056
zone_temp_zone_tem
AI:1
p
zone_temp_override_
AV:1
time_remaining
ai_10
AI:1010
ao1_fac_test
AV:91001
oat_ec_lockout
AV:9008
sat_ht_max
AV:83004
Modbus
Modbus Register
Modbus
Type
Register #