Sequence of Operation

Dehumidification

The RTU Open provides occupied and unoccupied dehumidification on units that are equipped with the Carrier
Humidi-MiZer™ option from the factory. This requires a space relative humidity sensor or a humidistat for control.
The following conditions must be true for the dehumidification control to operate:
The Outside Air Temperature is greater than the Cooling Lockout Temperature setpoint
The Indoor Fan has been on for at least 30 seconds
The unit has a valid Supply Air Temperature input
The unit has a valid Space Temperature input
The unit has a valid Space Relative Humidity Sensor or Humidistat input
Heat mode is not active and the time guard between modes has expired
When using a relative humidity sensor to control dehumidification, occupied and unoccupied dehumidification
setpoints are used.
When using a humidistat, the setpoints are not used. The humidistat indicates a high-humidity condition.
When a high indoor relative humidity condition is indicated and the above conditions are satisfied, the RTU Open
enters the dehumidification mode, energizing the Humidi-MiZer™ output.
The mode continues until the space relative humidity falls below the active setpoint by a 5% fixed Hysteresis when
a humidity sensor is used, or when there is no longer a call for dehumidification where a humidistat is used.
See the base unit / Humidi-MiZer™ operations manual for additional information.

Demand Limiting

The RTU Open may employ a demand limit strategy. Demand limiting in the RTU Open works through setpoint
expansion. The controller's heating and cooling setpoints are expanded in steps or levels. The degree to which the
setpoints are expanded is defined by the Demand Level Setpoints.
Each Demand Level (1 through 3) adjusts the heating and cooling setpoints outwards. By default, Demand 1
yields a 1 °F (.5 °C) expansion, Demand 2 yields a 2 °F (1.1 °C) expansion, and Demand 3 yields a 4 °F
(2.2 °C) expansion.
The BACnet Demand Limit variable sets the desired level of setpoint expansion in the receiving controller. Level 0
leaves the standard occupied and unoccupied heating and cooling setpoints in effect. Levels 1 through 3 expands
occupied heating and cooling setpoints.

Door switch

A Door Contact may be configured on any unused binary input. A typical application is a door or window contact
mounted within the space served by a single zone rooftop. The Door Contact disables mechanical cooling and any
heating, when active (an open door or window is detected). Economizer cooling, if available, continues to operate.
The input provides a configurable alarm delay (60 second default) before heating and cooling is disabled.