Appendix A: Network Points List for RTU Open
Point Name
Point
Access
SPT Sensor
R
Fan / Speed
R
Setpoint Adjustment
R/W
Range
Enthalpy (BACnet)
R/W
Optimal Start
R/W
Power Fail Restart Delay R/W
Indoor Air Quality CO2
R
(ppm)
Indoor Air Quality
R
Supply Air Temperature
R
Space Relative Humidity R
Space Temp Sensor
R
Outdoor Air Quality CO2
R
(ppm)
Gas Valve
R
Setpoint
R/W
RTU Open v5
Integration Guide
Units
Default
Value
0=Normal
1=Alarm
1=Off
2=Low
3=Med
4=High
5=On
°^F
5
0=High
Active
1=Low
(1)
hr
1
seconds
5
ppm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
0=Normal
1=Alarm
ppm
0=Normal
1=Alarm
°F
N2
N2
N2
Network
Network
Point
Point
Type
Address
BI
38
ADI
4
ADF
45
BO
6
ADF
61
ADF
58
ADF
31
BI
33
BI
47
BI
34
BI
46
ADF
37
BI
40
ADF
4
54
Lonworks
SNVT Type
SNVT Name
SNVT_count_inc(9)
nviSPAdjRng
SNVT_switch(95)
nviSysEnth
SNVT_count_inc(9)
nviOptmStart
SNVT_count_inc(9)
nviUntStrDly
SNVT_ppm(29)
nvoIAQ
SNVT_switch(95)
nvoIAQAlm
SNVT_switch(95)
nvoSATAlm
SNVT_switch(95)
nvoHiSPRHAlm
SNVT_switch(95)
nvoSPTmpSen
SNVT_ppm(29)
nvoOAQ
SNVT_switch(95)
nvoGasVlvAlm
SNVT_temp_p(105)
nviOccCoolSP
CARRIER CORPORATION ©2019
All rights reserved