To set up the RTU Open for the LonWorks Option Card (Part #LON-OC)

Turn off the RTU Open's power.
1
NOTES
Changes made to the switches when the controller is on will not take effect until the power has been
cycled!
The controller's rotary address switches are not used when the LON-OC is installed. That's because each
LON-OC has a 48-bit Neuron ID that makes it unique on the LonWorks network.
Set the SW3 DIP switches for LonWorks as follows:
2
8
Off
Plug the LonWorks Option Card's ribbon cable into Comm Option port J15 on the controller. See illustration
3
below.
CAUTION! The controller must be OFF before being connected.
Connect the LonWorks network to the LonWorks Option Card's 2-pin Net port.
4
NOTE The 2-pin Net port provides TP/FT-10 channel compatibility. The TP/FT-10 or "Free Topology" network
type is polarity insensitive. Use 24 to 16 AWG twisted pair wire.
Turn on the RTU Open's power.
5
Commission the controller for LonWorks communication. See instructions below.
6
RTU Open v5
Integration Guide
7
6
5
On
On
Off
17
4
3
On
Off
CARRIER CORPORATION ©2019
Communications wiring
2
1
Off
On
All rights reserved