Reading System Points
To verify that the system point is being written to within the refresh time specified (value varies by point), the i-
Vu® Open controller clears any value that is written, once it has been processed by the controller and returned
the system point to its default value. Therefore, a BAS should never read back the system point's value to confirm
the commanded value was successfully received. To confirm a write, refer to the table below for the corresponding
control point that should be read.
NOTE A confirming "read" should take place at least 30 seconds following the "write" to verify that the write has
been processed by the controller.
Commanded Points
Type /
Display Name
Instance
System Space
av:1902
Temperature
System Space
av:1904
RH
System Space
av:1903
AQ
System OA
av:1901
Temperature
[OA] Enthalpy
bv:1901
(BACnet)
System Outdoor
av:1908
AQ
System Water
av:1905
Temperature
†System
bv:1907
Fire/Smoke
†System
bv:1906
Pressurization
BAS On/Off
msv:1001
[Occupancy]
† Points do not apply to multi-protocol controllers.
RTU Open v5
Integration Guide
Control Points
Object Name
Display Name
system_spt
Space Temperature
- Prime Variable
system_rh
Space Relative
Humidity
system_iaq
Indoor Air Quality
CO2 (ppm)
system_oat
Outdoor Air
Temperature
oae
[OA] Enthalpy
Status
system_oaq
Outdoor Air Quality
CO2 (ppm)
system_water_t
Changeover Mode
emp
fire_shutdown
Fire/Smoke
Shutdown
press_override
Pressurization
keypad_ovrde
Occupancy Status
43
Appendix A: Network Points List for RTU Open
Type /
Object Name
Instance
av:2007
space_temp
av:1011
space_rh
av:1009
iaq
av:1003
oa_temp
bv:1002
enthalpy_status
av:1012
oaq
av:1014
chgovr_mode
bv:7007
fire_alarm
bv:7038
press_alarm
bv:2008
occ_status