Panasonic SC-HG1 Series Reference Manual page 74

For mitsubishi melsec iq-r series sequencer
Table of Contents

Advertisement

Error code
■ List of error codes
Error code
(hexadecimal)
The Station No. (i_uStationNo) is
100
outside the valid range
The information derived from the input
Start I/O No.(i_uStartIONo) and the
101
Station No. (i_uStationNo) is not
SC-HG1-C or SC-HG1-CEF.
Set to a controller where Set Controller
104
(i_uSetController) is set to 0 or does not
exist
Write Lever Ratio (i_uLeverRatio) is
10E
outside the valid range
200
Remote READY flag OFF
Execution Command (i_bEN) turned
201
OFF before normal or error completion
Execution Command (i_bEN) was
turned from ON to OFF and then turned
202
from OFF to ON while Execution Status
(o_bENO) was ON
FFFF
Module error occurrence
Description
SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
For CC-Link master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 64.
For CC-Link IE Field master/local module
Set the Station No. (i_uStationNo) to a value from 1 to 120.
Check if the Start I/O No.(i_uStartIONo) and the Station
No. (i_uStationNo) settings correctly indicate the target
communication unit.
Make the value of Set Controller (i_uSetController) greater
than 0.
Check if the setting is not applied to a controller beyond the
maximum number of connected units. Also, check if the
15th bit of Set Controller (i_uSetController) is not ON.
Specify a value within the valid range.
Check whether or not an error has occurred in the
communication unit.
Check if the Start I/O No.(i_uStartIONo) and the Station
No. (i_uStationNo) settings correctly indicate the target
communication unit.
Check that Normal Completion (o_bOK) or Error
Completion (o_bErr) has turned ON and then turn OFF
Execution Command (i_bEN). This error code is output
also when Execution Command (i_bEN) is intentionally
turned OFF before completion.
Check that Execution Status (o_bENO) turned OFF and
then turn ON Execution Command (i_bEN).
Check the Module Error Code (o_ud16ModuleErrId). For
information on module error codes, see "Appendix 2.4
Module error code (o_u16ModuleErrId) list".
74/184
Meaning
WUME-SCHG1IQRFB-1

Advertisement

Table of Contents
loading

Table of Contents