Appendix 2.2.
Connection error (SC-HG1-CEF)
If the communication with the CC-Link IE Field master/local module fails or a module error occurs, you can check the
error with the indicators of SC-HG1-CEF.
Common to both normal mode and network number setting mode
Indicator
Status
Power
supply
OFF
Power supply error
indicator
(Green)
STS2
indicator
ON
Mode selection error
(Red)
At the time of setting the network number
Indicator
Status
STS2
indicator
ON
Network number setting error
(Red)
Description of error
Description of error
SC-HG1 Series FB Library Reference Manual for Mitsubishi MELSEC iQ-R series Sequencer
Check the power supply wiring.
Check whether or not the power (24V) is supplied to the
communication unit.
The power supply capacity varies depending on the
controller type and the number of connected controllers.
Confirm the specifications of the connected controllers.
Check if the mode setting switch is correctly set.
Check whether or not the network number setting is outside
the valid range.
153/184
Meaning
Meaning