PWR
Bulk Charging
FAULT
Settings/Info...
CHG
INV
Figure 5-7, Bulk Charging Mode
Bulk Charging – The battery charger is delivering maximum current
(determined by the Setup 03C Max Charge Rate setting) to the batteries. The
charger will remain in Bulk charge until the absorb voltage (determined by
the Setup 03B Battery Type setting) is achieved.
PWR
Absorb Charging
FAULT
Settings/Info...
CHG
INV
Figure 5-8, Absorb Charging Mode
Absorb Charging - The Absorb charge state is the constant voltage
stage and begins when the absorb voltage is reached (determined by the
Setup 03B Battery Type setting) while Bulk Charging. During this stage,
the DC charging current decreases in order to maintain the absorb voltage
setting. This charge stage continues until 03E Absorb Done (Time, Amps or
SOC) or 03F Max Charge Time is reached.
PWR
Float Charging
FAULT
Settings/Info...
CHG
INV
Figure 5-9, Float Charging Mode
Float Charging – At the end of the Absorb Charge time, the charger
reduces the charge voltage and tries to maintain the batteries at the Float
charge voltage setting; which is determined by the Setup 03B Battery Type
setting as shown in Table 3-3, Battery Type to Charge Voltages.
Info: If the battery voltage falls ≤12.1 VDC (12-volt models), ≤24.2
VDC (24-volt models) or ≤48.4 VDC (48-volt models); the unit will
initiate bulk charging.
© 2010 Magnum Energy, Inc.
5.0 Operation
Bulk Charging appears on LCD; PWR
(green) is on solid and CHG (green)
LED is typically on solid, but may blink
slowly; FAULT (red) LED is off; INV
(green) LED could be on or off.
Absorb Charging appears on LCD;
PWR (green) is on solid and CHG (green)
LED is typically on solid, but may blink
slowly; FAULT (red) LED is off and INV
(green) LED could be on or off.
Float Charging appears on LCD; PWR
(green) LED is on solid and CHG (green)
LED is typically on solid, but may blink
slowly; FAULT (red) LED is off and INV
(green) LED could be on or off.
43