5.0 Operation
5.3.3.2 Stacking Fault Messages –
A fault condition may occur when two Inverters are stacked in series - using
the stacking interface to provide 120/240VAC output - that is not possible
on a single inverter installation. Refer to the following fault messages to help
troubleshoot the Inverters.
PWR
StackClock Fault
FAULT
Settings/Info...
CHG
INV

Figure 5-30, StackClock Fault

StackClock Fault - 1. There is a stacker cable problem; or, 2. One
inverter is losing synchronization with the other inverter.
Remedy: 1. Ensure you are using a Magnum Stacking Cable (this is
not a telephone/data cable, this is a custom made cable). 2. Inspect
the stacker cable and reconnect at both ends (listen and make sure
you hear an audible "click" from the connectors at both Inverters).
Info: This fault has been known to occur when a Magnum Energy
accessory is plugged into the Stack Port, but the installation is not
using multiple Inverters in a stacked confi guration. If this occurs,
perform an inverter reset (see section 6.2).
PWR
Stack Mode Fault
FAULT
Settings/Info...
CHG
INV

Figure 5-31, Stack Mode Fault

Stack Mode Fault - This unit has detected a problem with the "other"
stacked inverter, check that unit for a fault condition.
Remedy: This fault will automatically clear when the fault with the
other inverter is corrected.
PWR
StackPhase Fault
FAULT
Settings/Info...
CHG
INV

Figure 5-32, StackPhase Fault

StackPhase Fault - 1. The AC input wiring is incorrect; or, 2. One
phase was lost from the AC input source; or, 3. One of the inverter's internal
transfer relay is bad; or, 4. The inverter's AC input circuit breaker may be
open.
Remedy: If this fault doesn't clear after checking these four recom-
mendations; perform an inverter reset (see section 6.2).
52
StackClock Fault appears on the
LCD and the FAULT (red) LED is on.
The PWR (green), CHG (green) and
INV (green) LED's are off.
Stack Mode Fault appears on the
LCD and the FAULT (red) LED is on.
The PWR (green), CHG (green) and
INV (green) LED's are off.
StackPhase Fault appears on the
LCD and the FAULT (red) LED is on.
The PWR (green), CHG (green) and
INV (green) LED's are off.