Master Programming Level
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following
screen will be displayed:
Pressing 1 for Type will display the following screens:
While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the Escape
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining
relays.
Pressing 2 for Latching will toggle the display between Latching Yes and No.
If Latching Yes is selected, when the Relay is activated, the condition causing the activation must be
cleared and the FACP must be reset to clear the Relay.
If Latching No is selected, when the Relay is activated, the Relay will reset as soon as the condition
causing the activation is cleared. The FACP does not need to be reset.
3.5.6 System Setup
System Setup allows the programmer to configure the following control panel features:
Timers: This option allows the programmer to set the Soak 1, Soak 2, Waterflow and AC Loss
time delays.
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout to a user defined readout when the control panel is in Normal condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. If the Trouble
Reminder feature is not enabled and a trouble condition is not cleared within 24 hours, the
panel will reactivate the trouble sounder an send an Abnormal 24 hour Test message via the
optional communicator.
Charger Disable: This option allows the programmer to disable the onboard battery charger in
the event an external battery charger is being used.
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to "Canadian Option" on page 66).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
ANN-SECONDARY: This option allows the use of a secondary ANN-BUS with the ANN-SEC
option module. This option must be enabled if the ANN-SEC option card is installed on J13 of
the main circuit board.
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
1=TYPE
2=LATCHING
Relay Programming Screen
RELAY TYPE
1=ALARM
2=TROUBLE
3=SUPERVISORY
Relay Screen #1
RELAY #
ALARM
NO
RELAY TYPE
1=FUTURE USE
2=DISCHARGE
3=AC LOSS
Relay Screen #2
Programming
61