Connecting The Control Unit To The Lon - Viessmann Vitocrossal 300 Service Instructions For Contractors

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
Reduced room temperature
90
A
C
D
Example 2: Adjustment of reduced room
temperature from 5 °C to 14 °C
A Boiler water temperature or flow
temperature in °C
B Outside temperature in °C

Connecting the control unit to the LON

The LON communication module
(accessories) must be plugged in.
Installation instructions
LON communication module
Note
The data transfer via LON can take sev-
eral minutes.
Single boiler system with
Vitotronic 200-H and Vitocom 300
(example)
Set the LON subscriber numbers and
further functions via code 2 (see the fol-
lowing table).
52
-20
B
E
(cont.)
C Set room temperature in °C
D Heating circuit pump "OFF"
E Heating circuit pump "ON"
Adjustment of the reduced room tem-
perature:
Operating instructions
Note
In the same LON system, the same num-
ber cannot be allocated twice.
Only one Vitotronic may be program-
med as fault manager.