Viessmann Vitocrossal 300 Service Instructions For Contractors page 101

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
E7
Burner in a fault
state
E8
Burner in a fault
state
EA
Burner in a fault
state
Cause
Ionisation current
too low during cali-
bration
The ionisation cur-
rent lies outside the
permissible range
Ionisation current
outside permissi-
ble range during
calibration (devia-
tion from previous
level too great)
Troubleshooting
Measures
Check ionisation elec-
trode:
■ Distance to burner
gauze assembly (see
page 21)
■ Contamination of elec-
trode
■ Connecting lead and
plug-in connections
Check flue system; rem-
edy flue gas recirculation
if required.
Press reset button R
Check gas supply (gas
pressure and gas flow lim-
iter), gas train and con-
necting lead.
Check allocation of gas
type (see page 12).
Check ionisation elec-
trode:
■ Distance to burner
gauze assembly (see
page 21)
■ Contamination of elec-
trode
Press reset button R
Check flue system; rem-
edy flue gas recirculation
if required.
In open flue mode, pre-
vent very dusty conditions
for the combustion air.
Press reset button R.
Following several unsuc-
cessful reset attempts,
replace boiler coding card
and press reset button R.
101