Code 1
Heating circuit 1, heating circuit 2, heating...
Parameter
With heating circuit pump logic function:
address b5:...
Heating circuit pump "Off"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
Flow temperature minimum limit
C5:20
Electronic minimum flow
temperature limit 20 °C
Flow temperature maximum limit
C6:74
Electronic maximum flow
temperature limit set to
74 °C
Heating program - changeover
d5:0
External heating program
changeover changes to
"Constant operation with
reduced room tempera-
ture" or "Standby mode"
Ext. heating program changeover to heating circuit
d8:0
No heating program
changeover via extension
EA1
64
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
> RT
- 1 K
actual
set
> RT
- 2 K
actual
set
Heating circuit pump "On"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d5:1
The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture" (subject to coding
address 3A, 3b and 3C)
d8:1
Heating program change-
over via input DE1 at exten-
sion EA1
d8:2
Heating program change-
over via input DE2 at exten-
sion EA1
d8:3
Heating program change-
over via input DE3 at exten-
sion EA1
(cont.)
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
- 1 K
set
- 2 K
set
- 3 K
set