Viessmann Vitocrossal 300 Service Instructions For Contractors page 64

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Code 1
Heating circuit 1, heating circuit 2, heating...
Parameter
With heating circuit pump logic function:
address b5:...
Heating circuit pump "Off"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
Flow temperature minimum limit
C5:20
Electronic minimum flow
temperature limit 20 °C
Flow temperature maximum limit
C6:74
Electronic maximum flow
temperature limit set to
74 °C
Heating program - changeover
d5:0
External heating program
changeover changes to
"Constant operation with
reduced room tempera-
ture" or "Standby mode"
Ext. heating program changeover to heating circuit
d8:0
No heating program
changeover via extension
EA1
64
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
> RT
- 1 K
actual
set
> RT
- 2 K
actual
set
Heating circuit pump "On"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d5:1
The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture" (subject to coding
address 3A, 3b and 3C)
d8:1
Heating program change-
over via input DE1 at exten-
sion EA1
d8:2
Heating program change-
over via input DE2 at exten-
sion EA1
d8:3
Heating program change-
over via input DE3 at exten-
sion EA1
(cont.)
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
- 1 K
set
- 2 K
set
- 3 K
set