Viessmann Vitocrossal 300 Service Instructions For Contractors page 109

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Repairs
(cont.)
20
10
8
6
4
2
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Checking the temperature limiter
If the burner control unit cannot be reset after a fault shutdown, although the boiler
water temperature is below approx. 85 °C, check the following:
47
1. Pull the leads from temperature lim-
iter fJ.
2. Check the sensor resistance and
compare it with the curve.
3. Replace the sensor in the case of
severe deviation.
2. Check the continuity of the tempera-
ture limiter with a multimeter.
3. Remove the faulty temperature lim-
iter.
4. Coat the replacement temperature
limiter with heat conducting paste
and install it.
5. After commissioning, press reset but-
ton R on the control unit.
Troubleshooting
109