Viessmann Vitocrossal 300 Service Instructions For Contractors page 79

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Solar
(cont.)
Coding in the delivered condition
07:0
Interval function of the
solar circuit pump
switched off
08:60
The solar circuit pump will
stop when the actual cyl-
inder temperature rea-
ches 60 °C (maximum
cylinder temperature).
09:130
The solar circuit pump
stops if the collector tem-
perature reaches 130 °C
(maximum collector tem-
perature to protect the
system components).
0A:5
To protect the system
components and heat
transfer medium, the
speed of the solar circuit
pump is reduced when
the differential between
the actual cylinder tem-
perature and set cylinder
temperature is less than
5 K.
0b:0
Collector frost protection
function switched off
0C:1
Delta T monitoring
switched on.
No flow rate captured in
the collector circuit, or
flow rate too low.
Possible change
07:1
Interval function of the
solar circuit pump switched
on.
To capture the collector
temperature more accu-
rately, the solar circuit
pump starts for short
cycles.
08:10
The maximum cylinder
to
temperature can be adjus-
08:90
ted from 10 to 90 °C
09:20
The temperature can be
to
adjusted from 20 to
09:200
200 °C
0A:0
The differential between
to
the set cylinder tempera-
0A:40
ture and the start point for
reducing the stagnation
time can be adjusted from
0 to 40 K.
0b:1
Collector frost protection
function switched on (not
required with Viessmann
heat transfer medium).
0C:0
Delta T monitoring
switched off.
Code 2
79