Viessmann Vitocrossal 300 Service Instructions For Contractors page 83

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Solar
(cont.)
Coding in the delivered condition
25:50
Stop temperature for
thermostat function
50 °C.
Start temperature for
thermostat function ≤
stop temperature for ther-
mostat function:
Thermostat function e.g.
for reheating. Switching
output sS is switched off
when the temperature at
sensor / exceeds the
start temperature for the
thermostat function.
Start temperature for
thermostat function >
stop temperature for ther-
mostat function:
Thermostat function e.g.
for utilising excess heat.
Switching output sS is
switched off when the
temperature at sen-
sor / falls below the
start temperature for the
thermostat function.
26:1
Priority for DHW cylinder
1 – with alternate heat-
ing
Only when setting code
20:8.
Possible change
25:0
Start temperature for ther-
to
mostat function is adjusta-
25:100
ble from 0 to 100 K
26:0
Priority for DHW cylinder 1
– without alternate heating
26:2
Priority for DHW cylinder 2
– without alternate heating
26:3
Priority for DHW cylinder 2
– with alternate heating
26:4
Alternate heating without
priority for one DHW cylin-
der
Code 2
83