Viessmann Vitocrossal 300 Service Instructions For Contractors page 97

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
92
No solar DHW heat-
ing
93
Control mode
94
No solar DHW heat-
ing
98
Control mode
99
Control mode
9A
No solar DHW heat-
ing
9b
Control mode
9C
No solar DHW heat-
ing
9E
Control mode
9F
Control mode
A7
Control mode as per
delivered condition
b0
Burner blocked
Cause
Short circuit, col-
lector temperature
sensor
Short circuit, cylin-
der temperature
sensor
Short circuit, cylin-
der temperature
sensor
Lead break, tem-
perature sensor /
Lead break, tem-
perature sensor
Lead break, collec-
tor temperature
sensor
Lead break, cylin-
der temperature
sensor
Lead break, cylin-
der temperature
sensor
No flow rate in col-
lector circuit or flow
rate too low, or
temperature limiter
has responded
Solar control mod-
ule or Vitosolic
faulty
Programming unit
faulty
Short circuit, flue
gas temperature
sensor
Troubleshooting
Measures
Check temperature sen-
sor & on solar control
module or Vitosolic sen-
sor
Check temperature sen-
sor at connection S3 to
Vitosolic 100
Check temperature sen-
sor % on solar control
module or Vitosolic sen-
sor
Check sensor / on solar
control module
Check sensor aÖ on solar
control module
Check temperature sen-
sor & on solar control
module or Vitosolic sen-
sor
Check temperature sen-
sor at connection S3 to
Vitosolic 100
Check temperature sen-
sor % on solar control
module or Vitosolic sen-
sor
Check solar circuit pump
and solar circuit. Acknowl-
edge fault message.
Replace solar control
module or Vitosolic
Replace programming
unit
Check flue gas tempera-
ture sensor
97