Troubleshooting
Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
F9
Burner in a fault
state
FA
Burner in a fault
state
FC
Burner in a fault
state
Fd
Burner in a fault
state
FE
Burner blocked or in a
fault state
FF
Burner blocked or in a
fault state
104
Cause
Fan speed too low
during burner start
Fan not at stand-
still
Gas train faulty,
faulty modulation
valve control or flue
gas path blocked
Fault, burner con-
trol unit
Boiler coding card
or main PCB faulty
Internal fault or
reset button R
blocked
Measures
Check fan, fan connecting
cables and power supply;
check fan control.
Press reset button R
Check fan, fan connecting
cables and fan control.
Press reset button R
Check gas train. Check
flue system.
Press reset button R
Check ignition electrodes
and connecting cables.
Check whether a strong
interference (EMC) field
exists near the appliance.
Press reset button R
Replace control unit if
fault persists.
Press reset button R
Replace boiler coding
card or control unit if the
fault persists.
Start the appliance again.
Replace the control unit if
the appliance will not
restart.