Viessmann Vitocrossal 300 Service Instructions For Contractors page 53

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Further details regarding the individual steps
Boiler control unit
LON
Subscriber no. 1
Code "77:1"
Control unit is fault
manager
Code "79:1"
Control unit transmits
the time
Code "7b:1"
Control unit transmits
outside temperature
Set code "97:2"
LON subscriber fault
monitoring
Code "9C:20"
Carrying out a LON subscriber check
Communication with the system devices connected to the fault manager is tested
with a subscriber check.
Preconditions:
■ The control unit must be programmed
as fault manager (code "79:1")
■ The LON subscriber number must be
programmed in all control units (see
page 53)
■ The LON subscriber list in the fault
manager must be up to date (see
page 53)
Carrying out a subscriber check:
1. Press OK and å simultaneously
for approx. 4 s.
Commissioning, inspection, maintenance
Vitotronic 200-H
LON
Subscriber no. 10
Code "77:10"
Control unit is not
fault manager
Code "79:0"
The control unit
receives the time
Set code "81:3"
The control unit
receives the outside
temperature
Set code "97:1"
LON subscriber fault
monitoring
Code "9C:20"
(cont.)
Vitotronic 200-H
LON
Subscriber no. 11
Set code "77:11"
Control unit is not
fault manager
Code "79:0"
The control unit
receives the time
Set code "81:3"
The control unit
receives the outside
temperature
Set code "97:1"
LON subscriber fault
monitoring
Code "9C:20"
2. "Service functions"
3. "Subscriber check"
Vitocom
Subscriber no.
99
Device is fault
manager
Device
receives the
time
53