Viessmann Vitocrossal 300 Service Instructions For Contractors page 88

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Code 2
Heating circuit 1, heating circuit 2, heating...
Parameter
With heating circuit pump logic function:
address b5:...
Heating circuit pump "Off"
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow
temperature limit 20 °C
C6:74
Electronic maximum flow
temperature limit set to
90 °C
d3:14
Heating curve slope =
1.4
d4:0
Heating curve level = 0
d5:0
External heating program
changeover changes to
"Constant operation with
reduced room tempera-
ture" or "Standby mode"
d6:0
Heating circuit pump
stays in control mode at
signal "External block-
ing"
d7:0
Heating circuit pump
stays in control mode at
signal "External
demand"
88
> RT
actual
set
> RT
- 1 K
actual
set
> RT
- 2 K
actual
set
Heating circuit pump "On"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d3:2
Heating curve slope adjust-
to
able from 0.2 to 3.5 (see
d3:35
page 49)
d4:–13
Heating curve level adjust-
to
able from –13 to 40 (see
d4:40
page 49)
d5:1
The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture" (subject to coding
address 3A, 3b and 3C)
d6:1
Heating circuit pump stops
at signal "External block-
ing" (subject to coding
addresses 3A, 3b and 3C)
d6:2
Heating circuit pump starts
at signal "External block-
ing" (subject to coding
addresses 3A, 3b and 3C)
d7:1
Heating circuit pump stops
at signal "External
demand" (subject to coding
addresses 3A, 3b and 3C)
d7:2
Heating circuit pump starts
at signal "External
demand" (subject to coding
addresses 3A, 3b and 3C)
(cont.)
- 1 K
set
- 2 K
set
- 3 K
set

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu3a

Table of Contents