Viessmann Vitocrossal 300 Service Instructions For Contractors page 81

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Solar
(cont.)
Coding in the delivered condition
12:20
Minimum collector tem-
perature 20 °C.
The solar circuit pump is
not started until the mini-
mum collector tempera-
ture set at the collector
temperature sensor is
exceeded.
20:0
No extended control func-
tions enabled
22:8
Start temperature differ-
ential for central heating
backup: 8 K.
Switching output sS is
switched on when the
temperature at sen-
sor / exceeds the tem-
perature at sensor aÖ by
the selected value.
Possible change
12:0
Minimum collector temper-
ature function switched off
12:1
The minimum collector
to
temperature is adjustable
12:90
from 1 to 90 °C
20:1
Auxiliary function for DHW
heating
20:2
Differential temperature
control 2
20:3
Differential temperature
control 2 and auxiliary func-
tion
20:4
Differential temperature
control 2 for central heating
backup
20:5
Thermostat function
20:6
Thermostat function and
auxiliary function
20:7
Solar heating via external
heat exchanger without
additional temperature
sensor
20:8
Solar heating via external
heat exchanger with addi-
tional temperature sensor
20:9
Solar heating of two DHW
cylinders
22:2
Start temperature differen-
to
tial for central heating
22:30
backup is adjustable from 2
to 30 K
Code 2
81