Fault Codes - Viessmann Vitocrossal 300 Service Instructions For Contractors

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Troubleshooting

Fault codes

Displayed
System characteris-
fault code
tics
10
Controls as if outside
temperature was
0 °C
18
Controls as if outside
temperature was
0 °C
30
Burner blocked
38
Burner blocked
40
Mixer closes
44
Mixer closes
48
Mixer closes
4C
Mixer closes
50
No DHW heating
58
No DHW heating
90
Control mode
91
Control mode
96
Cause
Short circuit, out-
side temperature
sensor
Lead break, out-
side temperature
sensor
Short circuit, boiler
water temperature
sensor
Lead break, boiler
water temperature
sensor
Short circuit, flow
temperature sen-
sor, heating circuit
2 (with mixer)
Short circuit, flow
temperature sen-
sor, heating circuit
3 (with mixer)
Lead break, flow
temperature sen-
sor, heating circuit
2 (with mixer)
Lead break, flow
temperature sen-
sor, heating circuit
3 (with mixer)
Short circuit, cylin-
der temperature
sensor
Lead break, cylin-
der temperature
sensor
Short circuit, tem-
perature sensor /
Short circuit, tem-
perature sensor
Measures
Check outside tempera-
ture sensor (see
page 105)
Check outside tempera-
ture sensor (see
page 105)
Check boiler water tem-
perature sensor (see
page 106)
Check boiler water tem-
perature sensor (see
page 106)
Check flow temperature
sensor
Check flow temperature
sensor
Check flow temperature
sensor
Check flow temperature
sensor
Check sensors (see
page 106)
Check sensors (see
page 106)
Check sensor / on solar
control module
Check sensor aÖ on solar
control module