Viessmann Vitocrossal 300 Service Instructions For Contractors page 90

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Code 2
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
FA:20
Raising the set boiler
water temperature or the
set flow temperature
when changing from
operation with reduced
room temperature to
operation with standard
room temperature, by
20 %. See example on
page 123
Fb:30
Duration for raising the
set boiler water tempera-
ture or the set flow tem-
perature (see coding
address "FA") 60 min.
See example on
page 123
90
Possible change
+10 to -60 °C
FA:0
Temperature rise adjusta-
to
ble from 0 to 50 %
FA:50
Fb:0
Duration adjustable from 0
to
to 300 min;
1 step ≙ 2 min
Fb:150
(cont.)