General
(cont.)
Coding in the delivered condition
3A:0
Function input DE1 at
extension EA1: Not
assigned
Possible change
36:2
Function output aBJ: DHW
circulation pump
3A:1
Function input DE1: Heat-
ing program - changeover
3A:2
Function input DE1: Exter-
nal demand with set flow
temperature.
Set flow temperature for
external demand: Code
9b.
Function, circulation pump
for cylinder heating: Cod-
ing address 5F
Function, heating circuit
pumps: Coding address
D7
3A:3
Function input DE1: Exter-
nal blocking.
Function, circulation pump
for cylinder heating: Cod-
ing address 5E
Function, heating circuit
pumps: Coding address
D6
3A:4
Function input DE1: Exter-
nal blocking with fault mes-
sage input
Function, circulation pump
for cylinder heating: Cod-
ing address 5E
Function, heating circuit
pumps: Coding address
D6
3A:5
Function input DE1: Fault
message input
3A:6
Function input DE1: Brief
operation, DHW circulation
pump (pushbutton func-
tion).
Code 2
69