Viessmann Vitocrossal 300 Service Instructions For Contractors page 71

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

General
(cont.)
Coding in the delivered condition
3C:0
Function input DE3 at
extension EA1: Not
assigned
Possible change
DHW circulation pump run-
time adjustment: Coding
address 3d
3C:1
Function input DE3: Heat-
ing program - changeover
3C:2
Function input DE3: Exter-
nal demand with set flow
temperature.
Set flow temperature for
external demand: Code
9b.
Function, circulation pump
for cylinder heating: Cod-
ing address 5F
Function, heating circuit
pumps: Coding address
D7
3C:3
Function input DE3: Exter-
nal blocking.
Function, circulation pump
for cylinder heating: Cod-
ing address 5F
Function, heating circuit
pumps: Coding address
D7
3C:4
Function input DE3: Exter-
nal blocking with fault mes-
sage input
Function, circulation pump
for cylinder heating: Cod-
ing address 5E
Function, heating circuit
pumps: Coding address
D6
3C:5
Function input DE3: Fault
message input
3C:6
Function input DE3: Brief
operation, DHW circulation
pump (pushbutton func-
tion).
Code 2
71