Viessmann Vitocrossal 300 Service Instructions For Contractors page 87

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
A9:7
With pump idle time:
Heating circuit pump
"Off" in case of set value
modification by changing
the operating mode or
changing the set room
temperature
b0:0
With remote control:
Heating mode/reduced
operation: Weather-com-
pensated (change code
only for the heating circuit
with mixer)
b2:8
With remote control and
for the heating circuit,
operation with room tem-
perature hook-up must be
programmed: Room influ-
ence factor 8 (change
code only for heating cir-
cuit with mixer)
b5:0
With remote control: No
room temperature-
dependent heating circuit
pump logic function
(change code only for
heating circuit with
mixer)
Parameter
With heating circuit pump logic function:
address b5:...
Heating circuit pump "Off"
1
RT
2
RT
3
RT
4
RT
5
RT
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
(cont.)
Possible change
A9:0
Without pump idle time
A9:1
With pump idle time;
to
adjustable from 1 to 15
A9:15
b0:1
Heating mode: Weather-
compensated
Reduced mode: With room
temperature hook-up
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
b2:0
Without room influence
b2:1
Room influence factor
to
adjustable from 1 to 64
b2:64
b5:1
Heating circuit pump logic
to
function, see the following
b5:8
table:
Heating circuit pump "On"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Code 2
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
87