Viessmann Vitocrossal 300 Service Instructions For Contractors page 80

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Code 2
Solar
(cont.)
Coding in the delivered condition
0d:1
Night circulation monitor-
ing switched on.
Unintentional flow rate is
captured in the collector
circuit (e.g. at night).
0E:1
Calculation of solar yield
with Viessmann heat
transfer medium
0F:70
The flow rate in the col-
lector circuit at the maxi-
mum pump speed is set
to 7 l/min.
10:0
Target temperature con-
trol switched off (see cod-
ing address 11)
11:50
Set cylinder temperature
for solar 50 °C.
■ Target temperature
control switched on
(code 10:1):
Temperature at which
the solar heated water
in the DHW cylinder is
to be stratified.
■ Extended control func-
tions set to heat two
DHW cylinders (code
20:8):
If the actual tempera-
ture of a DHW cylinder
reaches the selected
set cylinder tempera-
ture, heating is trans-
ferred to the second
DHW cylinder.
80
Possible change
0d:0
Night circulation monitor-
ing switched off.
0E:2
Calculation of solar yield
with water as heat transfer
medium (do not select as
operation is only possible
with Viessmann heat trans-
fer medium)
0E:0
Calculation of solar yield
switched off
0F:1
Flow rate in the collector
to
circuit adjustable from 0.1
0F:255
to 25.5 l/min
10:1
Target temperature control
switched on
11:10
The set cylinder tempera-
to
ture for solar can be adjus-
11:90
ted from 10 to 90 °C