Viessmann Vitocrossal 300 Service Instructions For Contractors page 100

Gas condensing boiler with matrix gas burner and lambda pro control, natural gas and lpg version open and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
dd
Control mode without
room influence
dE
Control mode without
room influence
dF
Control mode without
room influence
E0
Control mode
E1
Burner in a fault
state
E3
Burner in a fault
state
E4
Burner blocked
E5
Burner blocked
100
Cause
Lead break, room
temperature sen-
sor, heating circuit
1 (without mixer)
Lead break, room
temperature sen-
sor, heating circuit
2 (with mixer)
Lead break, room
temperature sen-
sor, heating circuit
3 (with mixer)
Fault external LON
subscriber
Ionisation current
too high during cal-
ibration
Heat transfer too
low during calibra-
tion.
Temperature lim-
iter caused shut-
down.
Fault, supply volt-
age 24 V
Fault, flame ampli-
fier
Measures
Check room temperature
sensor for heating circuit 1
and remote control set-
tings (see page 125)
Check room temperature
sensor for heating circuit 2
and remote control set-
tings (see page 125)
Check room temperature
sensor for heating circuit 3
and remote control set-
tings (see page 125)
Check connections and
LON subscribers
Check gap between ioni-
sation electrode and
burner gauze assembly
(see page 21).
In open flue mode, pre-
vent very dusty conditions
for the combustion air.
Press reset button R
Ensure adequate heat
transfer.
Press reset button R
Replace control unit
Replace control unit