R EDU NDA N CY CON FIG UR AT IO N
Network addresses must be set for both Primary and Backup Digital Gateway.

Table 9 Primary and Backup IP address setting

Set the slave address for the selected Fieldbus / Field network interface.
2.
Figure 27 MNavigate Fieldbus Slave address Parameterization for Primary and Backup Digital
Gateway
3 2
It is essential that the IP address setting for LAN 2 of Primary and Backup Digi-
tal Gateway is different (e.g. Primary = 192.168.200.100 / Backup =
192.168.200.101).
The same subnet mask is used because both Ethernet ports are connected to
the same Ethernet network for MView and MNavigate communication.
Digital Gateway LAN3 is not used for M10x applications.
R EDU NDA NCY
1 TG C90 80 04