R ED U ND A N C Y CO N F IG U R AT IO N
Network addresses must be set for both Primary and Backup MNS Digital Gateway.

Table 8 Primary and Backup IP address setting

• The same subnet mask is used because both Ethernet ports are connected to
2. Set the slave address for the selected Fieldbus / Field network interface.

Figure 24 MNavigate Fieldbus Slave address Parameterization for Primary and Backup MNS

Digital Gateway

2 8
It is essential that the IP address setting for LAN 2 of Primary and Backup MNS
Digital Gateway is different (e.g. Primary = 192.168.200.100 / Backup =
192.168.200.101).
the same Ethernet network for MView and MNavigate communication.
MNS Digital Gateway LAN3 is not used for M10x applications.
R E D U ND A N C Y
1TG C 9 0 8 0 0 4 M 0 2 0 1