DATA MAPP IN G
Modbus
Function
Code
2
2
2
2
2
2
2
2
2
2
2
2
2
Continued on the next page
1 TG C90 80 04
Modbus
Device
Register
Number
13671
128
13672
128
13673
128
13674
128
13675
128
13676
128
13677
128
13678
128
13679
128
13680
128
13681
128
13682
128
13683
128
Description
CCW or K2
Ready
Alarm
New Trip
Test
HW local
Bus local
Remote
DI0
DI1
DI2
DI3
DI4
D EFAULT DATA MAP
Remarks
1 = Motor Runs Coun-
ter Clockwise
1 = Off and Ready for
Operation. No
alarm/trip is available
1 = Any Alarm condi-
tion of protection or
supervision functions.
1 = Any Trip condition
of the protection or
supervision functions
1 = Main switch set to
test position. (Motor
cannot start)
1 = Control Access is
selected to hardwired
I/O from Local / Re-
mote input on M10x
1 = Control Access is
passed to any control
station on the switch-
gear control network.
1=Control Access is
passed to the Process
Control System
1= Digital Input 0 of
M10x is on
1= Digital Input 1 of
M10x is on
1= Digital Input 2 of
M10x is on
1= Digital Input 3 of
M10x is on
1= Digital Input 4 of
M10x is on