D EFAULT DATA MAP
Switching Commands
The following table details the commands that are required from the Master (DCS / PLC) to
be sent to the M10x in order to control the motor or feeder module.
Operation
Type
Control Access
Stop
Start
Start CW
Close (CF)
Open (Act)
Start CCW
Close (Close)
Reset
Table 29 Switching Commands sent from DCS to Digital Gateway
60
Description
Remote control
Bus-Local control
Stop, Open
Start
Start Clockwise
Close for Contactor Feeder applica-
tion
Open for Actuator application
Start Counterclockwise
Close for Actuator Application
Reset
DATA MAPP ING
Modbus
Remarks
Command
0x2100
M10x is controlled via
DCS.
0x2104
DCS allows control via
local HMI.
0x0201
Stops the M10x, Opens
contactor K1 for Con-
tactor Feeder applica-
tion
0x0202
Starts the M10x. Close
contactor K1
0x0203
Start the M10x Coun-
terclockwise. Close
contactor K2.
0x1100
Reset of all trips
1 TG C90 80 04