COM MU NI CAT IO N I NT ERFACE CON N ECTI ON
In addition to the terminating resistor, it is also required to install a shielding clamp for the
RS485 communication to reduce EMC disturbances. The following figure shows a sample of
the clamp that can be used for shielding purpose.
Figure 11 Shielding Clamp for RS485
M10x-TCP motor controller
The communication between Digital Gateway and M10x-TCP is established via Modbus TCP
protocol.
M10x-TCP supports standard star but also ring topology communication (MRP protocol, in
cases increased communication availability is required).
Figure 12 Hardware connection between Digital Gateway and M10x-TCP
Parameterization of communication setting in M10x can be done either via the MD panel on
the MNS module front or with a Laptop with 'MCUsetup' / 'MConfig' software tool installed.
For further detail on changing the setting, refer to "
1 TG C90 80 04
S WITCHG EAR B US NET WORK
M10x User Guide"
document.