Multiple Master In Modbus Tcp Applications; Failsafe; Figure 34 Parameter Window For Modbus Tcp Parameters In Mnavigate - ABB LVS Digital Manual

With m10x motor controller
Hide thumbs Also See for LVS Digital:
Table of Contents

Advertisement

FAI LS AF E

Figure 34 Parameter Window for MODBUS TCP parameters in MNavigate

Multiple Master in Modbus TCP applications

The Digital Gateway offers the possibility to support up to 4 MODBUS TCP masters. This
function can only be utilized if also the PCS or PLC MODBUS master supports such configura-
tion.

7.6. Failsafe

In circumstances where a disturbance in the MODBUS communication network needs to be
monitored it is possible to select a 'Failsafe' state for each M10x. This state must be
fined as a parameter for each M10x separately. The Digital Gateway supervises the MODBUS
communication to the PCS or PLC if the parameter PLC Time Out is set to "YES". The timeout
for this connection is set by using the parameter PLC Time Out (see Table 13 and 14 for initial
values).
The M10x must be operating in 'Remote' mode for the Failsafe function to be
active.
4 2
CO NF IG UR AT IO NS
de-
1 TG C90 80 04