R EDU NDA N CY
M10x Redundant Configuration
For M10x-M the parameter 'Redundancy Disabled/Enabled' must be set to 'Enabled' either
through MD panel on MNS / NeoGear module front or through MNavigate as shown in Table
8.
Note: In case of M10x-TCP this setting remains 'Disabled'.
Table 8 M10x-M redundant communication setting
Digital Gateway Redundant Configuration
Configuration and Parameterization of MNS Digital [Upgrade] projects are done via MNavi-
gate tool.
The parameters must then be downloaded to both the Primary and Backup Digital Gateway
to become effective.
In a project with multiple Digital Gateway most of the Digital Gateway parameter are identi-
cal. To ease the parameterization such parameters could be copied among the Digital Gate-
way (Assign to Digital Gateway).
As Network address settings are different between the Digital Gateway
same network those must be configured individually
The steps of configuring the redundant Digital Gateway is as following:
1. Set the Ethernet IP address of LAN1 and LAN2 for Primary and Backup Digital
Figure 26 MNavigate IP address Parameterization for Primary and Backup Digital Gateway
1 TG C90 80 04
MNavigate tool
R EDU NDA NCY CONFIG UR AT IO N
MCUSetup tool
s
if connected to the
Gateway.
31