Master Programming Level
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3
while viewing the Time-Date screen will cause the display to toggle between 12HR and 24HR.
Select 12HR for 12 hour display or 24HR for 24 hour display.
NOTE: If the clock is changed to 24 hour (military) format, the date will change to the European
standard of Day-Month-Year (for display purposes only).
Daylight Savings Time
TIME AND DATE
1=DAYLIGHT SAVINGS
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
Time & Date Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the
programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1
will select March, 2 will select April, and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will begin. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the
last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the
programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1
will select September, 2 will select October, and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the
programmer to select the week of the month that daylight savings time will end. In the first sub-
screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third
week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the
last week of the selected month.

Trouble Reminder

SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND
The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for
3=CHARGR DISABLE
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 61, for a
System Setup Screen #2
detailed description of this feature. Pressing 2 while viewing System Setup Screen #2 will cause the
display to toggle to Trouble Remind Yes, which enables this feature. Each press of the 2 key will
cause the display to toggle between Trouble Remind Yes and Trouble Remind No.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more
than 24 hours will cause the FACP to resound the trouble sounder.

Charger Disable

Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable
the onboard battery charger. If an external battery charger is being used, the onboard battery
charger must be disabled. Each press of the 3 key will toggle between Chargr Disable No and
Chargr Disable Yes.
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
Clock Format
DAYLIGHT SAVINGS
1=ENABLED
2=START MONTH
3=START WEEK
Daylight Savings Screen #1
DAYLIGHT SAVINGS
YES
1=END MONTH
MAR
2=END WEEK
WK 2
Daylight Savings Screen #2
Programming
NOV
WK 1