Banner - Honeywell Notifier RP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Master Programming Level
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
TIMER
1=AC LOSS DLAY 2 HR
The reporting of a loss of AC power can be delayed by programming the length of the desired
delay. Press 1 while viewing Timer Screen #2 to display the following:
Timer Screen #2
A flashing cursor will appear in the lower left corner of the display. The factory default setting is 02
hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When the second
digit is entered, the display will return to AC Loss Delay Screen #1.
NOTE: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC Loss
exist in the panel, the System Trouble relay will delay activation for the duration of the AC Loss
Delay setting.

Banner

SYSTEM SETUP
The top line of the display, which appears when the control panel is in normal mode, can be
1=FUTURE USE
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause
2=TIMERS
3=BANNER
the following to be displayed:
System Setup Screen #1
Pressing 1 while viewing the Select Banner Screen will display the following screen:
This screen allows the user to select the factory default Banner which will be displayed when the
system is in Normal Mode of operation. Press the Enter key to accept this as the default display.
Press the Escape key to cancel and return to the Select Banner Screen.
Pressing 2 while viewing the Select Banner Screen will display the following screen:
This screen allows the programmer to enter a custom banner. A flashing cursor will appear in the
bottom left corner of the display. A maximum of 20 characters (including spaces) can be entered
into the screen. After entering up to 20 characters in the screen, press Enter to store the entry. To
quickly clear the current banner, press the CLR key.
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
AC Loss Delay
AC LOSS DELAY
RANGE 00-24 HOURS
AC Loss Delay Screen #1
SELECT BANNER
1=FACTORY BANNER
2=USER BANNER
Select Banner Screen
FACTORY BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
USER BANNER-LINE 1
PRESS ENTER IF OK
User Defined Banner Screen
Programming
63