Honeywell Notifier RP-2001 Instruction Manual page 89

Pre-action/deluge control panel
Table of Contents

Advertisement

Calculating the System Current Draw
Table 5.3 contains three columns for calculating current draws. For maximum output current
available per circuit and per panel, refer to Section 1.2, "Specifications", on page 13. For each
column, calculate the current and enter the total (in amperes) in the bottom row. When finished,
copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 90.
Device Type
Primary, Non-Fire Alarm Current
Qty
Main Circuit Board
1
N-CAC-5X
[
4XTM
[
(1 max.)
ANN-SEC card
[
(1 max.)
N-ANN-80(C)
[
N-ANN-I/O
[
N-ANN-RLY
[
N-ANN-(R)LED
[
N-ANN-S/PG
[
2-wire Detector
[
Heads
4-wire Detector
[
Heads
Power Supervision
[
5
Relays
NAC #1
NAC #2
NAC #3
NAC #4
Current Draw from
TB9 (nonalarm)
6
Sum each column
for totals
1 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
2 The current shown represents one zone (IDC) on the main circuit board in alarm. One zone consumes 0.040
amps.
3 Refer to the Device Compatibility Document for standby current.
4 Enter the number of IDCs used minus one.
5 Must use compatible listed Power Supervision Relay.
6 Total current draw listed above cannot exceed 7.2 amps
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
Calculation Column 1
(amps)
X [current draw]=
Total
X[0.095]=
0.095
]
X[0.001]=
]
X[0.005]=
]
X[0.003]=
]
X[0.037]=
]
X[0.035]=
]
X[0.015]=
]
X[0.028]=
]
X[0.045]=
3
]
X[
]
=
3
]
X[
]
=
]
X[0.025]=
[
]=
Primary Non-Alarm =
Table 5.3 System Current Draw Calculations
Calculation Column 2
Secondary, Fire Alarm Current
(amps)
Qty
X [current draw] =
1, 2
1
X[0.221]
=
[
]
X[0.001]=
1
[
]
X[0.011]
=
[
]
X[0.003]=
(1 max.)
[
]
X[0.040]=
[
]
X[0.200]=
[
]
X[0.075]=
[
]
X[0.068]=
[
]
X[0.045]=
4
[
]
X[0.040=
4
[
]
X[0.040]=
[
]
X[0.025]=
[
]
X[
]=
[
]
X[
]=
[
]=
Secondary Alarm =
Power Supply Calculations
Calculation Column 3
Secondary, Non-Fire Alarm
Current
(amps)
Total
Qty
X [current draw]=
0.221
1
X[0.095]=
[
]
X[0.001]=
[
]
X[0.005]=
[
]
X[0.003]=
(1 max.)
[
]
X[0.015]=
[
]
X[0.035]=
[
]
X[0.015]=
[
]
X[0.028]=
[
]
X[0.045]=
3
[
]
X[
]
3
[
]
X[
]
[
]
X[0.025]=
[
]=
Secondary Non-Alarm =
Total
0.095
=
=
89