Ann-Bus Modules; Auto-Configure; Ann-S/Pg Options - Honeywell Notifier RP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Master Programming Level

ANN-BUS Modules

If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-
BUS addresses for the module(s). The following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen
with technical information about the selected module.
NOTE: When the Secondary ANN-BUS is enabled through System Setup programming, addresses
1 - 3 will be on the primary ANN-BUS and addresses 4 - 8 will be on the seconary ANN-BUS.
In the technical information screen, pressing 1 for Type will display the following screens:
Press the number corresponding to the module type, if any, that is installed with the selected
address. This will enable the module.

Auto-Configure

The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically
program the device type and address into the system. Pressing 3 while viewing ANN-BUS Screen
#1 will begin the Auto-Configure process and cause the following screen to be displayed:

ANN-S/PG Options

PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
The Printer Option allows the user to configure the optional printer. Pressing 1 while viewing the
3=ANN-80 OPTIONS
ANN-BUS Screen #2 will display the following screens:
ANN-BUS Screen #2
1=PORT
2=PRINTER SUPV
3=OFFLINE TIMER
Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select
between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the
display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that the
interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select an
offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print Options
screen #1. Each press of the 2 key will cause the display to toggle between Printer Supv NO for no
supervision and Printer Supv YES for printer supervision. Note that this option is not selectable if
the Serial Port option has been selected.
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
ANN-BUS MODULE TYPE
1=NONE
2=ANN-80
3=ANN-I/O
Module Type Screen #1
ANN-S/PG OPTIONS
PARALLEL
NO
60
Printer Options Screen #1
ANN-BUS MODULES
1=ADDR. 1
NONE
2=ADDR. 2
NONE
3=ADDR. 3
NONE
ANN-BUS Module Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
ANN-S/PG OPTIONS
1=BAUD RATE
N/A
2=DATA BITS
N/A
3=PARITY
N/A
Printer Options Screen #2
Programming
ANN-S/PG OPTIONS
1=STOP BITS
N/A
Printer Options Screen #3