Honeywell Notifier RP-2001 Instruction Manual page 110

Pre-action/deluge control panel
Table of Contents

Advertisement

FACP Configuration Templates
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 (Water-
flow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull Station) will
operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 3 (Low Pressure) will operate the Supervisory Relay
Device Installation Example for Template 7
Output Circuit #1
Alarm NAC
Output Circuit #2
Waterflow NAC
1
Notes:
1.
Waterflow Delay is programmed for 10 seconds.
2.
All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ˝ watt (PN: 71252).
3.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "N-CAC-5X Class A Converter Module" on page 29.
110
Input Circuit #1
2-Wire Smoke
Input Circuit #2
Fire (Heats)
Input Circuit #3
Low Pressure
Input Circuit #4
Waterflow
1
Input Circuit #5
Pull Station
Template 7: Single Hazard - Dual Zone
Output Circuit #4
Waterflow NAC
1
Output
Circuit #3
Input Circuit #6
Release
Manual Release
Solenoid 1
RP-2001 Series Manual — P/N 52985:D5 1/26/2017