Honeywell Notifier RP-2001 Instruction Manual page 32

Pre-action/deluge control panel
Table of Contents

Advertisement

Installation
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the FACP. In addition, the System Trouble indicator will turn on to
indicate the Disconnect condition.
NOTE: The 4XTM Module is not directly suitable for transmitting reverse polarity supervisory
signal. For an application using reverse polarity of a supervisory signal, refer to the Appendix titled
"FACP with Keltron" on page 118.
TBL Jumper
Disconnect
Switch
shown in
disconnect
position
32
Connect to FACP Connectors J4 & J5
Figure 2.14 4XTM Transmitter Module
Installation of Optional Modules
Polarities are shown for module activation
}
1+
Remote Alarm (power-limited)*
2-
}
3+
Remote Trouble (power-limited)*
4-
No connection
5
}
6+
Municipal Box (nonpower-limited)*
7-
* Wiring from these terminals
can exit the protected premises.
Dummy load terminals 6 and 7
(4.7kΩ, ¼ watt resistor) if
Municipal Box is not connected.
Disconnect LED
RP-2001 Series Manual — P/N 52985:D5 1/26/2017

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier rp-2001eNotifier rp-2001c

Table of Contents