Section 4: Operating Instructions

Factory programmed Templates have been provided to facilitate the installation and configuration
of the Fire Alarm Control Panel. The factory default programming for this panel is Template #1.
Refer to "FACP Configuration Templates" on page 96 for a detailed description of the FACP
operation for Template #1.

4.1 Panel Control Buttons

4.1.1 Acknowledge/Step
The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to
steady and also changes the status field on the LCD display from capital letters to small letters
(TROUBL to Troubl). When the piezo is silenced, an acknowledge message is sent to the printer and
the history file. Acknowledge also sends a silence piezo command to the optional annunciators
connected to the FACP. The Acknowledge key will have no effect on the Notification Appliance
Circuits.
When more than one event exists, the first press of the Acknowledge/Step key functions as
described in the preceding paragraph. Subsequent pressing of the key steps through each active
event.
4.1.2 Alarm Silenced (Domestic/Export Versions)/Signal Silence
(Canadian Version)
The Alarm Silenced/Signal Silence key performs the same functions as Acknowledge/Step, except
it will not step through each event when multiple events are present at the panel. In addition, if an
alarm exists, it turns off all silenceable NACs (Notification Appliance Circuits) and causes the
Alarm Silenced indicator to turn on. It also sends an 'alarm silenced' message to the printer, history
file and optional annunciators. A subsequent new alarm will resound the system NACs. The Alarm
Silenced indicator is turned off by pressing the Reset key, the Drill key, or subsequent activation of
the NACs.
NOTES:
1. If Silence Inhibit has been enabled, NACs cannot be silenced for one minute following initiation
of an alarm.
2. When the system is configured for dual hazard operation, an alarm in one hazard area may
reactivate notification appliance circuits programmed for that area only.
4.1.3 Drill/Hold 2 Sec (Domestic/Export Versions)/Alarm Signal
(Canadian Version)
When the Drill/Alarm Signal key is held for a minimum of two seconds (time required to prevent
accidental activations), the FACP turns on all NAC outputs and turns off the Alarm Silenced
indicator if it was previously on. The EVAC IN SYSTEM message is shown on the LCD display.
The same message is sent to the printer and history file. The Alarm Silence/Signal Silence key can
be used to turn off all silenceable NAC outputs following activation by the Drill/Alarm Signal key.
4.1.4 Reset
Pressing and releasing the Reset key turns off all NACs, temporarily turns off resettable power to 4-
wire detectors, causes a RESET IN SYSTEM message to be displayed on the LCD and sends the
same message to the printer and history file. It also performs a lamp test by turning on all LEDs,
piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that